Electric Chiller
February 3, 2024Specifications
Capacity:
30-3300 ton
Gas Pressure:
2.3-7.3 Psi (Standard)
Dual Fuel Burner
Gas and Oil, Low NOx, <10ppm
Exhaust Pressure Drop :
3 – 8 Inch W.C.
Exhaust Temperature:
560-990 F
Cooling / Heating
Domestic Hot Water
Detailed Specifications
Single Stage:
BDH Model, Single Stage Hot Water Driven
- Capacity: 30-1800 ton
- Hot Water Temperature: 160-220 F (Standard)
- Hot water Valve
- Cooling Only
BDE Model, Single Stage Exhaust Driven
- Capacity:30-1163 ton
- Exhaust Temperature: 450 – 600 F
- Cooling Only
BDS Model, Single Stage Steam Driven
- Capacity: 30-2000 ton
- Steam Pressure: 6.0-60 Psi (Standard)
- Offer Steam Valve
- Cooling Only
Two Stage:
BZ Model, Direct Gas Fired
- Capacity: 30-3300 ton
- Gas Pressure: 2.3-7.3 Psi (Standard)
- Dual Fuel Burner (Gas and Oil, Low NOx, <10ppm)
- Cooling / Heating / Domestic Hot Water
BS Model, Steam Driven
- Capacity:30-3300 ton
- Steam Pressure: 60 – 150 Psi
- Chiller Come With Steam Valve
- Cooling Only
BE Model, Exhaust Driven
- Capacity:40-3300 ton
- Exhaust Pressure Drop: 3 – 8 Inch W.C.
- Exhaust Temperature: 536-990F
- Cooling / Heating Only
BH Model, Hot Water Driven
- Capacity:30-3300 ton
- Hot Water Temperature: 280 – 356 F
- Provides Hot Water Valve
- Cooling Only
Multi-Energy:
BZE Model, Exhaust and Direct Fired
- Capacity: 30-3300 ton
- Gas Pressure: 2.3-7.3 Psi (Standard)
- Dual Fuel Burner (Gas and Oil, Low NOx, <10ppm)
- Exhaust Pressure Drop : 3 – 8 Inch W.C.
- Exhaust Temperature: 560-990 F
- Cooling / Heating / Domestic Hot Water
BHE Model, Hot (Jacket) Water and Exhaust
- Capacity: 30-3300 ton
- Hot Water Temperature: 160-220 F (Standard)
- Exhaust Pressure Drop: 3 – 8 Inch W.C.
- Exhaust Temperature: 580-1200 F
BZHE Model, Hot (Jacket) Water and Exhaust + Direct Gas Fire
- Capacity: 30-3300 ton
- Gas Pressure: 2.3-7.3 Psi (Standard)
- Dual Fuel Burner (Gas and Oil, Low NOx, <10ppm)
- Exhaust Pressure Drop : 3 – 8 Inch W.C.
- Exhaust Temperature: 580-1200 F
- Hot Water Temperature: 190-220 F (Standard)